DT-A Series 40KVA 3/3 Phase HF UPS
❤ Add to collection

DT-A Series 40KVA 3/3 Phase HF UPS

DSP Control, True IGBT Rectifier 3 Phase UPS

0.00
¥0.00
¥0.00
¥0.00
Weight:0.00KG
Quantity:
(Inventory99999)
Buy Now!
Add to cart
Description

DSP Control, True IGBT Rectifier 3 Phase UPS


1. System Introduction

DT Series is a true full digitized IGBT rectifier double conversion online UPS.It has parallel redundant features.With THDI≤5%,output power factor 0.9-1,and overall efficiency AC-AC up to 95%,DT Series can be defined as a high reliability and efficiency green power.It also integrates friendly user communication interface and remote-control system,which is ideal for medium to large data centers, precision equipment, and Telecomm industry.


2. System Features

2.1 High Performance Index

Advanced IGBT Rectifier and HF PFC technology, input THDI≤5%, input power factor≥0.99 to save more energy;

DT Series adapts the 5th generation IGBT Inverter control technology to enhance the output voltage/current performance. Online 3 Phase Input and output double conversian structure to adapt 380/400/415V,50/60Hz Mains Grid Supply 5ystems.
Output Power Factor 0.9-1 to carry 12.5%load capacities than traditional UPS.
Wide Input Voltage Range 138-485 Vac (305~485Vac non-derating,138~305Vac linear derating)with40-7OHz Frequency Range. High adaptive capacity and Generator Capability with ratio of 1.2:1.

Overall Efficiency upto 95%,Can reach to 98%on ECO Mode.
Powerful overload ability with output short circuit protection;110%-120%overloads for 10 mins.125%-150%for 1 min.

◆ Intelligent battery management to extend battery life.Dual DSP control to correct charging parameters,which provides optimized charging solutions based on operational mode,such as float charge or equalized charge.Flexible Battery Configuration.It can be set on the front panel with 30-50 Units of Batteries.

2.2 Safe, Reliable and Easy Maintenance

DT Series adapts dual DSP technology to control UPS all kinds of power function processes (including Parallel functian)in order to increase system reliability.
◆ Flexible Single or Dual Utility Power Input to comprehensively protect load devices.
◆ Battery Misconnection protection. UPS will not be damaged by reverting the polarities connection.
◆ Self-Evaluation and Alarm of Phase Misconnection or Lost.
◆ 100% 3 Phase Unbalanced Allowance Design.
◆ Front Modular Maintenance Design. MTBF can be upto 300K Hours.
◆ 90% of system components are from international famous brands. All devices has been aged and fully tested for at least 24 hours before leaving the factory.


3. Application Type

DT Series is designed for small and medium important equipment/application systems, such as SME data exchange centers, communication equipment industry, and precision instruments.

ModelDT400L33-A
Capacity40KVA/36KW
   Host Machine Specification
UPS Structure  Online Double Conversion
Appearance  High Frequency Online Design
Overall Efficiency (AC-AC)  >95%
Noise(In 2 Meters)  <50-65dB
Working Temp  -10-40℃
Storage Temp  -25~60℃ without derating
Humidity  <95%Non-Condesing
National Standard  GB4943
International Standard  EN 50091-1/2, EN62040-1, EN62040-2, EN62040-3
Parallel Redundancy  Parallel Redundancy Up to 8 Units
ProtectionOverload, Short-Circuit, Over Temp, Utility Power Voltage High/Low, BAT Voltage High/Low
DC Start  Available
Generator Compatibility  Available
Display  LCD Color Touch Screen (multi-language)+LED
Mute  Auto
Cabinet Standard  IP20
Cooling System  Intelligent Speed Control Cooling Fan
Elevation  1500M without derated
  Rectifier Specification
Input Voltage  380Vac+N+W, 3 Phase
Input Voltage Range  138~485Vac; 305~485Wsc non-derating;138~305Vac linear derating
Input Frequency Range  40-70Hz
Soft-Start  >20 Seconds
Input PF  0.99
THDI  <3.5%
  Output Specification
Output Voltage  line Voltage:380× 1±1% AC or Phase Voltage:220× 1±1% AC
Output Power Factor  0.9 (30-36 pieces battery configuration) or 1 (36-50 pieces configuration)
Output Voltage Regulation  380vac±1%(Statitc Laad); 380Vac ±2%(50-0% Sudden Change); 380Vac±3%(100-0%%Sudden Change)
Output Frequency  Grid mode: Input synchronization (Frequency range can be set ±1%, ±2%, ±4%,±5 or±10%); Battery Mode:50 or 60×(1±0.02%)Hz
Distortion  <2%(Linear Full Load), <4%(Non-Linear Full Load)
3 Phase Unbalanced  Allow 3 Phase 100%Unbalanced
Output Volt Unbalanced Degree  ≤1%(Balanced Load); ≤2%(50% Balanced Load)
Inputv/Output Phase Swift  ≤1%(Balanced Load); ≤2%(50% Balanced Load)
Frequency Tracking Range  40-70Hz
Output Waveform  Pure Sine Wave
Overload

<125%; More than 10 mins

>125%; More than 1 min

>150%:More than 300ms transfer to bypass
Crest Ratio  3:1
Efficiency  >95%
Short-Circuit  Circuit Auto-Protection, Bypass Switch Tripping
Output Abnormal  INV.Output Auto-Locked Protection
  Bypass Specification
Static Bypass Transfer Time  0ms
Static Bypass Input Range  380Vac(-15~+15%(Maximum +25% and ~45%)
Frequency Range  ±1Hz, ±2Hz, ±3Hz Selectable
Bypass ... >INV Transfer Time  0ms
Frequency Tracking Speed  0.5~2hz/s
Manual Maintenance Bypass  Available
  Battery Specification
Type  Sealed Lead Acid Maintenance Free
BAT Rated Volts/Units  ±180V/ ±192V/ ±204V/ ±216V/ ±228V/ ±240V/ ±252V/ ±264V /±276V/ ±288V/ ±300Vdc(30-50Pcs)
BAT Low  Shutdown Protection
  Communication Specification
Communication Port  RS232/ SNMP/ 485/ Dry Contact (Optional Accessory)
Remote Software  Multi-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control
  Physical Parameters
External Model Size mm (WxDxH)250*710*530
Net Weight Kg38