Contact Us!
Current Page:
BH-T 20KVA Series HF Online 3/1 Phase
❤ Add to collection

BH-T 20KVA Series HF Online 3/1 Phase

Full Digital Controlled HF Online UPS

0.00
¥0.00
¥0.00
¥0.00
Weight:0.00KG
Quantity:
(Inventory99999)
Buy Now!
Add to cart
Description

Full Digital Controlled HF Online UPS


System Introduction

BH-T Series is a double conversion 1 Phase In/1 Phase Out, 3 Phase In/ 1 Phase Out pure online new generation UPS with DSP design and has been integrated with an intelligent digitized management process. It has been designed for mainstream double conversion system with N+1 or N+X parallel redundancy feature, and manufactured with advanced SMT international standard, which provide outstanding stability and reliability. This high-frequency switching power technology will bring UPS developments into the next level.

 

Main Features

High Performance Index

◆ Latest HF switching power supply rectifier and PFC Technology. Input Power Factor 0.99,THDI≤5%

◆ Wide Input Range from 150~500Vac(Phase to Phase) or 90-300Vac(Phase to Neutral) on full load.

◆ Latest lGBT technology to achieve high overall efficiency up to 94%.Compatible with 220/230/240V and 50/60 Hz Grid Supply Systems.

◆ Powerful overload ability with output short circuit protection technology: 125% overload for 10 minutes, > 150% overload for 0.5 seconds.

◆ Can be connected with all kinds of generators to save customers costs.

◆ Intelligent temperature compensator and low wave charger can extend battery lifetime.

◆ Intuitive dual LCD and LED display panels, which comprehensively and intuitively reflect the state of powers system statuses,parameters, and other information. Users can modify and operate based on individual needs on these friendly displays.

◆ 19" inch Rack Mount structure design.It can be compatible with standard communication cabinet to greatly save data room spaces.

◆ Reliable Design made with strong Glass fiber base (FR4) double side PCB, greatly improve reliability in harsh environment,Well designedventilation and conformal coating , avoid dust accumulation ,improve resistant to corrosion.

◆ Versatile Input Phase Configuration. System works with 1 OR 3-phases mains input ,without complex setting or power derating.

 

Safe and Reliable

BH Series adapts DSP technology to control UPS all kinds of power function processes (including Parallel function) in order to increase system reliability.

BH Series adapts sensitive peak current protection circuit design to protect the system from damages due to short-circuit, cold load impacts.

 90% of system components are from international famous brands. All devices has been aged and fully tested for at least 24 hours before leaving the factory.

 

Rich Optional Accessories

BH Series can use SNMP Network Adapter, RS485/Dry Contact, USB port, and EPO function to build up a remote control and monitoring system.

 


Technology Points

  • Full-Digitized DSP Control to enhance system integration and reliability.

  • Wide Input Voltage and frequency range to increase the high capability to utility power grid.

  • Advanced Battery Management System to extend battery lifetime.

  • High Loads Compatibility and Output Overload Ability to ensure safety

  • Dot-Matrix LCD display panels, which comprehensively and intuitively reflect the state of power system statuses, parameters, and other information. 

BH200L31-T / BH200L31-T-RM

20KVA/18KW

Host Machine Specification

UPS Structure
Double Conversion High Frequency Online
Appearance
Tower or Rack-Mount Type
Overall Efficiency (AC-AC )
> 94%
Noise(In 2 meters)
< 50dB
Working Temp
0 ~ 40℃
Storage Temp
-25 ~ 60℃(Without BAT)
Humidity
< 95% Non Condensing
Safety Standard
GB/T 14715
EMC Standard
EN 50091/ EN 62040-1/2
Protections
Overload, Short-Circuit, Over Temp., Utility Power Voltage High/low, BAT Voltage High/low
Parallel Redundancy
None
Generator CompatibilityAvailable
DC Start Available
Manual Maintenance Bypass Optional Accessory
Display 

LCD display: Input/ Output /Bypass Status, ECO Mode, Charging Status, Load Status, Rectifier Status, INV.Temp

Alarm Auto
Mute
Auto

Rectifier Specification

Input Voltage Range

Phase to Neutral 90~300VAC; Phase to Phase 150~500VAC

Input Frequency Range
40-70Hz(Auto Tracking)
Input PF
0.99
THDI

2%(Linear Load); <7%(Non-Linear Load)

Output Specification

Output Voltage
220/230/240Vac Adjustable
Output PF
0.9(No Lag)
Output Voltage Regulation
220Vac±1%(Static Load); 220Vac±2%(50-0% Sudden Change); 220Vac±3%(100-0% Sudden Change)
Output Freq.(Online Mode)
When 46Hz ≤Input Freq.≤ 54Hz,Input Freq.=Output Freq.; When Input Freq.54Hz, Locked at 50Hz
Output Freq. (BAT Mode)
50/60Hz± 0.2%
Output Waveform
Pure Sine wave
Distortion
< 2%(Linear Full Load), < 7%(100% Non-Linear Load)
Overload

105%~125%: 10 min

125%~150%: 60s

> 150%: 0.55s
Crest Ratio
3∶1
Efficiency
> 94%
Short-Circuit
Circuit Auto Protection, Output Voltage/Current 0
Output Abnormal
INV Output Auto-Locked Protection
Noise Suppression
EMI/RFI Wave filter
BAT Low
Shutdown Protection
Dynamic Response
3% at full load,recovering in 20-60ms
Auto-Restart
Available
Software Control
Available

Bypass Specification

Static Bypass Transfer Time
0 ms
Static Bypass Range
80Vac± 5%~285Vac±5%
Bypass -> INV Transfer Time
2ms

Battery Specification

Type
Sealed Lead Acid Maintenance Free
Ext. Model Rated Volts
192~240Vdc
Ext. Model Charging Current
4A

Communication Specification

Communication Port
RS232 (Std.);/SNMP/RS485/Dry Contact (Optional Accessory)
Remote Software
Multi-functional Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control

Physical Parameters

Ext. Model Tower Size mm(D×W×H)
550×240×530
Ext. Net Weight Kg
26.1