BH-T 2KVA Series HF Online 1/1 Phase
❤ Add to collection

BH-T 2KVA Series HF Online 1/1 Phase

Full Digital Controlled HF Oneline UPS

0.00
¥0.00
¥0.00
¥0.00
Weight:0.00KG
Quantity:
(Inventory99999)
Buy Now!
Add to cart
Description

Full Digital Controlled HF Oneline UPS


System Introduction

BH-T Series is a digital controlled online double conversion, 1/1 Phase pure sine wave online UPS, with smart design and highreliable, this system overall efficiency > 90%, BH-T series can bedefined as a high cost effective and reliability and energy saving green power.

 

Main Features

High Performance Index

◆ Latest HF switching power supply rectifier and PFC Technology. Input Power Factor 0.99,THDI≤5%

◆ Wide Input Range from 150~500Vac(Phase to Phase) or 90-300Vac(Phase to Neutral) on full load.

◆ Latest lGBT technology to achieve high overall efficiency up to 94%.Compatible with 220/230/240V and 50/60 Hz Grid Supply Systems.

◆ Powerful overload ability with output short circuit protection technology: 125% overload for 10 minutes, > 150% overload for 0.5 seconds.

◆ Can be connected with all kinds of generators to save customers costs.

◆ Intelligent temperature compensator and low wave charger can extend battery lifetime.

◆ Intuitive dual LCD and LED display panels, which comprehensively and intuitively reflect the state of powers system statuses,parameters, and other information. Users can modify and operate based on individual needs on these friendly displays.

◆ 19" inch Rack Mount structure design.It can be compatible with standard communication cabinet to greatly save data room spaces.

◆ Reliable Design made with strong Glass fiber base (FR4) double side PCB, greatly improve reliability in harsh environment,Well designedventilation and conformal coating , avoid dust accumulation ,improve resistant to corrosion.

◆ Versatile Input Phase Configuration. System works with 1 OR 3-phases mains input ,without complex setting or power derating.

 

Safe and Reliable

BH Series adapts DSP technology to control UPS all kinds of power function processes (including Parallel function) in order to increase system reliability.

BH Series adapts sensitive peak current protection circuit design to protect the system from damages due to short-circuit, cold load impacts.

 90% of system components are from international famous brands. All devices has been aged and fully tested for at least 24 hours before leaving the factory.

 

Rich Optional Accessories

BH Series can use SNMP Network Adapter, RS485/Dry Contact, USB port, and EPO function to build up a remote control and monitoring system.

Technology Points

  • Full-Digitized DSP Control to enhance system integration and reliability.

  • Wide Input Voltage and frequency range to increase the high capability to utility power grid.

  • Advanced Battery Management System to extend battery lifetime.

  • High Loads Compatibility and Output Overload Ability to ensure safety

  • Dot-Matrix LCD display panels, which comprehensively and intuitively reflect the state of power system statuses, parameters, and other information. 

ModelBH10S/BH10LBH20S/BH20LBH30S/BH30LBH60S/BH60LBH100S/BH100L
BH10S/L-RMBH20S/L-RMBH30S/L-RMBH60S/L-RMBH100S/L-RM
Capacity1KVA/0.8KW2KVA/1.6KW3KVA/2.4KW6KVA/5.4KW10KVA/9KW
Host Machine Specification
UPS StructureOnline Double   Conversion High Frequency
AppearanceTower or Rack Mount   Type
Overall Efficiency> 90%
Noise(In   2 meters)<   50dB
Working Temp0~40℃
Storage Temp-15-60℃(without batteries)
Safety StandardGB/T 14715
EMC   StandardEN 50091 /EN 62040-1/2
ProtectionOverload, Short-Circuit, Over Temp., Utility   Power Voltage High/Low, BAT Voltage High/Low
Parallel RedundancyNone
Generator CompatibilityAvailable
DC startAvailable
Maintenance BypassNone
DisplayLCD Display: Input/   Output /Bypass Status,ECO Mode, Charging Status, Load Status, Rectifier   Status, INV. Temp
AlarmAuto
MuteAuto
Rectifier Specification
Input   Voltage Range100% Load: 160~300Vac,   50% Load:90~300Vac
Input Frequency Range40~70Hz(Auto Tracking)
Input PF0.99
THDI<3% Linear   load, < 5% Non-Linear Load
Output Specification
Output Voltage220Vac(220/230/240Vac Available)
Output PF0.8/0.9(No Lag)
Output Voltage Regulation220Vac±1%(Static   Load); 220Vac±2%(50-0% Sudden Change); 220Vac±3%(100-0% Sudden   Change)
Output Freq(utility)When 46Hz≤Input Freq.≤54Hz, Output Freq.=Input Freq.;   When Input Freq.<46Hz or >54Hz, Locked at 50Hz
Output   Freq(BAT Model)50Hz±0.2%
Output   WaveformPure   sine wave
Distortion< 2%(Linear Full   Load), < 7%(100%  Non-Linear Full Load)
Overload>125% : 30S
    >150%: 0.5S Transfer to Bypass
>120%: More than 1 Min
    >150%: 300ms Transfer to Bypass
Crest Ratio3∶1
Inverter Efficiency> 90%
Short CircuitCircuit Auto   Protection, Output Voltage/Current 0
Output AbnormalINV.   Output Auto-Locked Protection
Noise SuppressionEMI/RFI Wave   Filter
Battery Voltage LowShut Down Protection
Dynamic Response3% at full load,   Recovering in 20ms
Auto Restart FunctionAvailable
Software Set On/OffAvailable
Bypass Specification
Static Bypass Transfer Time0ms
Static Bypass Range80Vac±5%~285Vac±5%
Bypass -> INV Transfer Time<2ms
Battery Specification
TypeSealed   Lead Acid Maintenance Free
Model Rated Volts/Units12V 7/9Ah*2P12V 7/9Ah*4P12V 7/9Ah*6P12V 7/9Ah*16P
Std. Built-in BAT Type  Backup Time5-10mim5-10mim5-10mim5-15mim5-15mim
Ext. Model Rated Voltage36Vdc72Vdc96Vdc192 Vdc Defult /240Vdc   (Optional)
Charging CurrentStd.Built-in model 1A, Ext. model 4A
Communication Specification
Communication PortStd.RS232;   SNMP/485/Dry Contact(Optional   Accessory)
Remote SoftwareMulti-functional   Monitoring System, Online and BAT Mode Status, BAT Fault, Remote Control
Physical Parameters
Size(W×D×H)mmStd. Type145×318×220145×318×220190×370×320190×5500×460
Ext. Type145×390×220190×535×340
RM/RT Type440×360×88/2U440×500×88/2U
Net Weight KGTower
    Std./ Ext. Type
9 / 4.514 / 621.6 / 8.346.5 / 14.846.5 / 16
RM/RT  
    Std./ Ext. Type
13 / 8.518.5 / 11.5- / 12- / 14.6- / 15